SE509 Ultrasonic Flow Meter

Introduction

 

SE509 ultrasonic energy meter, which is used for measuring individual energy consumption in any liquid heating/cooling systems. The meter is supplied complete with flowmeter and temperature sensor, which can makes the system real-time detect the temperature of supply and return pipe.

The temperature sensor is to use conversion element characteristics of electromagnetic parameters change with temperature, the temperature and temperature related parameters for testing device.The resistance-change of the temperature change can be converted to known as thermal resistance sensors.

  SE509 Meter provides highly accurate thermal energy measurement in chilled water, hot water and condenser water systems based on signal inputs from two temperature sensors and ultrasonic flow meters.  

 

 

Features

2.2"TFT LCD

320x240 Color screen with multilevel backlight adjust-ments, clear data readable in both blight and dark environ-ments.

Keypad Area

Four touch buttons with easy operating logic.

Sockets

For power supply, output and transducers lines.Protective, not easy to fall off, stable and reliable connection process.

 
 

 

 

 

 

Wiring Diagram

 

 

 

 

 

Product Dimension

 

 

 

Technical Data

 

Technical Parameter

 

Velocity Range

0~40ft/s (0~12m/s)

Accuracy

±1.0%

Repeatability

0.2%

Pipe Size

1" ~ 80" (DN25 ~ DN2000)

Liquid

Water, sea water, oil, alcohol...

Pipe Material

PVC, stainless steel, carbon steel, copper...

Output

Analog output: ModBus RS485,OCT,4~20mA, max load 750Ω.

Power Supply

24V DC

Energy Unit

Giga Joule(GJ),Kilocalorie(KC),KWh,BTU

Keypad

Four touch keys

Display

2.2 inch TFT LCD 320*240

Temperature

Transmitter: -40℉~140℉ (-40℃~60℃)

 

Transducer: -40℉~176℉ (-40℃~80℃)

 

PT1000 Temp. Sensor: 35.6℉~221℉ (2℃~105℃)

Humidity

0 to 95% RH,non-condensing

Transmitter

IP54

Transducer

Encapsulated design, IP68

 

Standard cable length: 5m

 

Ordering Information

 

SE509

Code

Specification

 

 

 

 

 

 

 

 

 

A Ultrasonic Energy(BTU) Meter

 

 

 

 

 

 

 

 

Code

Transmitter enclosure area classification

1

IP65, die-cast aluminum machined enclosure

2

Explosion-proof enclosure , Ex dia II BT4

 

 

 

 

 

Code

Cable Length

L

Standard cable length: 33ft(10m)

L+

On request other lengths

 

 

Code

Temperature Sensor

PT1000

Temperature: 35.6℉~221℉ (2℃~105℃)

 
SE509 A 1 L PT1000 Complete ordering information

 

 

 

Package Content

 

 

 

Installation

 

 

V Method

The V method is considered as the standard method. It usually gives a more accurate reading and is used on pipe diameters ranging from 25mm to 400mm (1~16”)approximately. Also,it is convenient to use, but still requires proper installation of the transducer, contact on the pipe at the pipe's centerline and equal spacing on either side of the centerline.

Z Method

The V method is considered as the standard method. It usually gives a more accurate reading and is used on pipe diameters ranging from 25mm to 400mm (1~16”)approximately. Also,it is convenient to use, but still requires proper installation of the transducer, contact on the pipe at the pipe's centerline and equal spacing on either side of the centerline.

N Method

With the N method, the sound waves traverse the fluid twice and bounce three times off the pipe walls. It is suitable for small pipe diameter measurement. The measurement accuracy can be improved by extending the transit distance with the N method
(uncommonly used).

W Method

As with the N method, the measurement accuracy can also be improved by extending the transit distance with the W method. The sound wave traverses the fluid four times and bounces four times off the pipe walls. It is suitable for very small pipe(diameters less than 50mm,2")

 

 

Application Industry

 

 

Cooling Tower

  • Cooling water circulation systems

  • Inlet and outlet pipelines

  • Monitoring and control systems

  • Water quality monitoring

Aquaculture

 

  • Nutrient solution proportioning

 

  • Water disinfection in recirculating systems

  • Aquaculture environment monitoring

  • Drainage variation monitoring

Chemical Industry

 

  • Inbound and outbound raw materials

  • Reaction and separation process control

  • Utility engineering and environmental monitoring

  • Special conditions and media measurement

HVAC

  • Automated process control

  • Large scale metering projects

  • School, shopping mall, museum, university, office building

Swimming Pools
  • Monitoring of drainage flow
  • Leak detection
  • Energy-saving management

 

 

 

 

Velocity Range: 0~±40ft/s (0~±12m/s)
Accuracy: ±1.0%
Pipe Size: 1'' ~ 80'' (DN25 ~ DN2000)
Liquid: water, sea water, diesel oil, alcohol...
Pipe Material: PVC, stainless steel, carbon steel, copper...
Output: 4-20mA
Power Supply: 24V DC
Display: 2.2 inch TFT LCD 320*240